12.14.5 Settings
Table 252: SPVNZBAT Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Enabled Disable/Enable Operation
RtdBattVolt 20.00 - 250.00 V 1.00 110.00 Battery rated voltage
BattVoltLowLim 60 - 140 %Vbat 1 70 Lower limit for the battery terminal voltage
BattVoltHiLim 60 - 140 %Vbat 1 120 Upper limit for the battery terminal voltage
tDelay 0.000 - 60.000 s 0.001 0.200 Delay time for alarm
tReset 0.000 - 60.000 s 0.001 0.000 Time delay for reset of alarm
12.14.6 Measured values
Table 253: SPVNZBAT Measured values
Name Type Default Description
V_BATT REAL 0.00 Battery terminal voltage that has to be supervised
BLOCK BOOLEAN 0 Blocks all the output signals of the function
12.14.7 Monitored Data
Table 254: SPVNZBAT Monitored data
Name
Type Values (Range) Unit Description
BATTVOLT REAL - kV Service value of the battery
terminal voltage
12.14.8 Operation principle
The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are Enable and Disable.
The function execution requires that at least one of the function outputs
is connected in configuration.
The operation of the station battery supervision function can be described by using a
module diagram. All the modules in the diagram are explained in the next sections.