Name Values (Range) Unit Step Default Description
IndicationMa15 Hide
Show
- - Hide Indication mask for binary channel 15
TrigLevel16 Trig on 0
Trig on 1
- - Trig on 1 Trigger on positive (1) or negative (0) slope
for binary input 16
IndicationMa16 Hide
Show
- - Hide Indication mask for binary channel 16
12.3.6 Operation principle
Disturbance report DRPRDRE is a common name for several functions to supply the
operator, analysis engineer, and so on, with sufficient information about events in the
system.
The functions included in the disturbance report are:
Sequential of events
Indications
Event recorder
Trip value recorder
Disturbance recorder
Figure 114 shows the relations between Disturbance Report, included functions and
function blocks. Sequential of events , Event recorder and Indications uses information
from the binary input function blocks (BxRBDR). Trip value recorder uses analog
information from the analog input function blocks (AxRADR). Disturbance recorder
DRPRDRE acquires information from both AxRADR and BxRBDR.
Section 12 1MRK 505 277-UUS C
Monitoring
274
Technical Manual