12.15.4 Signals
Inputs PRESSURE and TEMP together with settings PressAlmLimit,
PressLOLimit, TempAlarmLimit and TempLOLimit are not supported in
this release of 650 series.
12.15.4.1 SSIMG InputSignals
Table 256: Input signals for the function block SSIMG (GM01-)
Signal Description
BLOCK Block of function
BLK_ALM Block all the alarms
PRESSURE Pressure input from CB
TEMP Temperature of the insulation medium from CB
PRES_ALM Pressure alarm signal
PRES_LO Pressure lockout signal
SET_P_LO Set pressure lockout
SET_T_LO Set temperature lockout
RESET_LO Reset pressure and temperature lockout
12.15.4.2 SSIMG OutputSignals
Table 257: Output signals for the function block SSIMG (GM01-)
Signal
Description
PRESSURE Pressure service value
PRES_ALM Pressure below alarm level
PRES_LO Pressure below lockout level
TEMP Temperature of the insulation medium
TEMP_ALM Temperature above alarm level
TEMP_LO Temperature above lockout level
1MRK 505 277-UUS C Section 12
Monitoring
313