EasyManua.ls Logo

ABB REB650 - Settings

ABB REB650
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 350: 3PHSUM Output signals
Name Type Description
AI3P GROUP SIGNAL Linear combination of two connected three phase inputs
AI1 GROUP SIGNAL Linear combination of input 1 signals from both SMAI
blocks
AI2 GROUP SIGNAL Linear combination of input 2 signals from both SMAI
blocks
AI3 GROUP SIGNAL Linear combination of input 3 signals from both SMAI
blocks
AI4 GROUP SIGNAL Linear combination of input 4 signals from both SMAI
blocks
15.10.5 Settings
Table 351: 3PHSUM Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global Base Value
groups
SummationType Group1+Group2
Group1-Group2
Group2-Group1
-(Group1+Group2)
- - Group1+Group2 Summation type
DFTReference InternalDFTRef
DFTRefGrp1
External DFT ref
- - InternalDFTRef DFT reference
Table 352: 3PHSUM Non group settings (advanced)
Name
Values (Range) Unit Step Default Description
FreqMeasMinVal 5 - 200 % 1 10 Magnitude limit for frequency calculation in %
of Vbase
15.10.6 Operation principle
Summation block 3 phase 3PHSUM receives the three-phase signals from Signal
matrix for analog inputs function (SMAI). In the same way, the BLOCK input will
reset all the outputs of the function to 0.
15.11 Global base values GBASVAL
Section 15 1MRK 505 277-UUS C
Basic IED functions
408
Technical Manual

Table of Contents

Other manuals for ABB REB650

Related product manuals