Name Values (Range) Unit Step Default Description
OscillationTime6 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 6
Threshold7 6 - 900 %VB 1 65 Threshold in percentage of station battery
voltage for input 7
DebounceTime7 0.000 - 0.100 s 0.001 0.005 Debounce time for input 7
OscillationCount7 0 - 255 - 1 0 Oscillation count for input 7
OscillationTime7 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 7
Threshold8 6 - 900 %VB 1 65 Threshold in percentage of station battery
voltage for input 8
DebounceTime8 0.000 - 0.100 s 0.001 0.005 Debounce time for input 8
DebounceTime8 0 - 255 - 1 0 Oscillation count for input 8
OscillationTime8 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 8
Threshold9 6 - 900 %VB 1 65 Threshold in percentage of station battery
voltage for input 9
DebounceTime9 0.000 - 0.100 s 0.001 0.005 Debounce time for input 9
OscillationCount9 0 - 255 - 1 0 Oscillation count for input 9
OscillationTime9 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 9
4.1.3.2 Setting parameters for communication module
Table 8: COM05_12BI Non group settings (basic)
Name
Values (Range) Unit Step Default Description
BatteryVoltage 24 - 250 V 1 110 Station battery voltage
Table 9: COM05_12BI Non group settings (advanced)
Name
Values (Range) Unit Step Default Description
Threshold1 6 - 900 %VB 1 65 Threshold in percentage of station battery
voltage for input 1
DebounceTime1 0.000 - 0.100 s 0.001 0.005 Debounce time for input 1
OscillationCount1 0 - 255 - 1 0 Oscillation count for input 1
OscillationTime1 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 1
Threshold2 6 - 900 %VB 1 65 Threshold in percentage of station battery
voltage for input 2
DebounceTime2 0.000 - 0.100 s 0.001 0.005 Debounce time for input 2
OscillationCount2 0 - 255 - 1 0 Oscillation count for input 2
OscillationTime2 0.000 - 600.000 s 0.001 0.000 Oscillation time for input 2
Threshold3 6 - 900 %VB 1 65 Threshold in percentage of station battery
voltage for input 3
DebounceTime3 0.000 - 0.100 s 0.001 0.005 Debounce time for input 3
Table continues on next page
1MRK 505 277-UUS C Section 4
Binary input and output modules
43
Technical Manual