IEC 60870-5-103 protocol can be configured to use either the optical serial or RS485
serial communication interface on the COM05 communication module. The functions
Operation selection for optical serial (OPTICALPROT) and Operation selection for
RS485 (RS485PROT) are used to select the communication interface.
See the Engineering manual for IEC103 60870-5-103 engineering
procedures in PCM600.
The functions IEC60870-5-103 Optical serial communication (OPTICAL103) and
IEC60870-5-103 serial communication for RS485 (RS485103) are used to configure
the communication parameters for either the optical serial or RS485 serial
communication interfaces.
14.9.2 Settings
Table 317: OPTICAL103 Non group settings (basic)
Name Values (Range) Unit Step Default Description
SlaveAddress 1 - 31 - 1 1 Slave address
BaudRate 9600 Bd
19200 Bd
- - 9600 Bd Baudrate on serial line
RevPolarity Disabled
Enabled
- - Enabled Invert polarity
CycMeasRepTime 1.0 - 1800.0 s 0.1 5.0 Cyclic reporting time of measurments
MasterTimeDomain UTC
Local
Local with DST
- - UTC Master time domain
TimeSyncMode IEDTime
LinMastTime
IEDTimeSkew
- - IEDTime Time synchronization mode
EvalTimeAccuracy Disabled
5ms
10ms
20ms
40ms
- - 5ms Evaluate time accuracy for invalid time
EventRepMode SeqOfEvent
HiPriSpont
- - SeqOfEvent Event reporting mode
Table 318: RS485103 Non group settings (basic)
Name
Values (Range) Unit Step Default Description
SlaveAddress 1 - 31 - 1 1 Slave address
BaudRate 9600 Bd
19200 Bd
- - 9600 Bd Baudrate on serial line
CycMeasRepTime 1.0 - 1800.0 s 0.1 5.0 Cyclic reporting time of measurments
Table continues on next page
Section 14 1MRK 505 277-UUS C
Station communication
370
Technical Manual