Function block
TIMERSET
INPUT ON
OFF
IEC09000290-1-en.vsd
IEC09000290 V1 EN
Figure 88: TIMERSET function block
Signals
Table 153: TIMERSET Input signals
Name Type Default Description
INPUT BOOLEAN 0 Input signal
Table 154: TIMERSET Output signals
Name Type Description
ON BOOLEAN Output signal, pick-up delayed
OFF BOOLEAN Output signal, drop-out delayed
Settings
Table 155: TIMERSET Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
t 0.000 - 90000.000 s 0.001 0.000 Delay for settable timer n
11.3.1.9 AND function block
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
AND function block AND - -
Functionality
The AND function is used to form general combinatory expressions with boolean
variables. The AND function block has four inputs and two outputs.
1MRK 505 277-UUS C Section 11