15.14.3.2 Function block
DOSLAN1
LINKUP
WARNING
ALARM
IEC09000134-1-en.vsd
IEC09000134 V1 EN
Figure 173: DOSLAN1 function block
15.14.3.3 Signals
Table 358: DOSLAN1 Output signals
Name Type Description
LINKUP BOOLEAN Ethernet link status
WARNING BOOLEAN Frame rate is higher than normal state
ALARM BOOLEAN Frame rate is higher than throttle state
15.14.3.4 Settings
The function does not have any parameters available in the local HMI or PCM600.
15.14.3.5 Monitored data
Table 359: DOSLAN1 Monitored data
Name
Type Values (Range) Unit Description
State INTEGER 0=Off
1=Normal
2=Throttle
3=DiscardLow
4=DiscardAll
5=StopPoll
- Frame rate control state
Quota INTEGER - % Quota level in percent 0-100
IPPackRecNorm INTEGER - - Number of IP packets
received in normal mode
IPPackRecPoll INTEGER - - Number of IP packets
received in polled mode
IPPackDisc INTEGER - - Number of IP packets
discarded
Table continues on next page
1MRK 505 277-UUS C Section 15
Basic IED functions
415
Technical Manual