12.11.6 Monitored data
Table 239: MVGGIO Monitored data
Name Type Values (Range) Unit Description
VALUE REAL - - Magnitude of deadband value
RANGE INTEGER 0=Normal
1=High
2=Low
3=High-High
4=Low-Low
- Range
12.11.7 Operation principle
Upon receiving an analog signal at its input, IEC61850 generic communication I/O
functions (MVGGIO) will give the instantaneous value of the signal and the range, as
output values. In the same time, it will send over IEC 61850-8-1 the value, to other
IEC 61850 clients in the substation.
12.12 Measured value expander block MVEXP
12.12.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Measured value expander block MVEXP - -
12.12.2 Functionality
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU
and VNMMXU), current and voltage sequence measurement functions (CMSQI and
VMSQI) and IEC 61850 generic communication I/O functions (MVGGIO) are
provided with measurement supervision functionality. All measured values can be
supervised with four settable limits: low-low limit, low limit, high limit and high-high
limit. The measure value expander block has been introduced to enable translating the
integer output signal from the measuring functions to 5 binary signals: below low-low
limit, below low limit, normal, above high-high limit or above high limit. The output
signals can be used as conditions in the configurable logic or for alarming purpose.
1MRK 505 277-UUS C Section 12
Monitoring
297