12.9.4 Signals
Table 233: SPGGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN BOOLEAN 0 Input status
12.9.5 Settings
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
12.9.6 Operation principle
Upon receiving a signal at its input, IEC61850 generic communication I/O functions
(SPGGIO) function sends the signal over IEC 61850-8-1 to the equipment or system
that requests this signal. To get the signal, PCM600 must be used to define which
function block in which equipment or system should receive this information.
12.10 IEC 61850 generic communication I/O functions 16
inputs SP16GGIO
12.10.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
IEC 61850 generic communication I/O
functions 16 inputs
SP16GGIO - -
12.10.2 Functionality
IEC 61850 generic communication I/O functions 16 inputs (SP16GGIO) function is
used to send up to 16 logical signals to other systems or equipment in the substation.
Section 12 1MRK 505 277-UUS C
Monitoring
292
Technical Manual