EasyManua.ls Logo

ABB REB650 - Energizing Inputs

ABB REB650
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17.3 Energizing inputs
Table 383: Energizing inputs
Description Value
Rated frequency 50/60 Hz
Operating range Rated frequency ± 5 Hz
Current inputs Rated current, I
n
0.1/0.5 A
1)
1/5 A
2)
Thermal withstand capability:
Continuously 4 A 20 A
For 1 s 100 A 500 A *)
For 10 s 20 A 100 A
Dynamic current withstand:
Half-wave value 250 A 1250 A
Input impedance <100 mΩ <20 mΩ
Voltage inputs Rated voltage, V
n
100 V AC/ 110 V AC/ 115 V AC/ 120 V AC
Voltage withstand:
Continuous 420 V rms
For 10 s 450 V rms
Burden at rated voltage <0.05 VA
*) max. 350 A for 1 s when COMBITEST test switch is included.
1) Residual current
2) Phase currents or residual current
17.4 Binary inputs
Table 384: Binary inputs
Description
Value
Operating range Maximum input voltage 300 V DC
Rated voltage 24...250 V DC
Current drain 1.6...1.8 mA
Power consumption/input <0.38 W
Threshold voltage 15...221 V DC (parametrizable in the range in steps of
1% of the rated voltage)
Section 17 1MRK 505 277-UUS C
Technical data
450
Technical Manual

Table of Contents

Other manuals for ABB REB650