12.12.3 Function block
MVEXP
RANGE* HIGHHIGH
HIGH
NORMAL
LOW
LOWLOW
IEC09000215-1-en.vsd
IEC09000215 V1 EN
Figure 119: MVEXP function block
12.12.4 Signals
Table 240: MVEXP Input signals
Name Type Default Description
RANGE INTEGER 0 Measured value range
Table 241: MVEXP Output signals
Name
Type Description
HIGHHIGH BOOLEAN Measured value is above high-high limit
HIGH BOOLEAN Measured value is between high and high-high limit
NORMAL BOOLEAN Measured value is between high and low limit
LOW BOOLEAN Measured value is between low and low-low limit
LOWLOW BOOLEAN Measured value is below low-low limit
12.12.5 Settings
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
GlobalBaseSel: Selects the global base value group used by the function to define
(IBase), (VBase) and (SBase).
12.12.6 Operation principle
The input signal must be connected to a range output of a measuring function block
(CVMMXN, CMMXU, VMMXU, VNMMXU, CMSQI, VMSQ or MVGGIO). The
function block converts the input integer value to five binary output signals according
to table 242.
Section 12 1MRK 505 277-UUS C
Monitoring
298