7.1.7 Operation principle
The protection design can be decomposed in four parts:
The direction element
The harmonic Restraint Blocking function
The four step over current function
The mode selection
If VT inputs are not available or not connected, setting parameter
DirModeSelx shall be left to default value, Non-directional.
en05000740_ansi.vsd
Direction
Element
4 step over current
element
One element for each
step
Harmonic
Restraint
Mode Selection
dirPhAFlt
dirPhBFlt
dirPhCFlt
harmRestrBlock
enableDir
enableStep1-4
DirectionalMode1-4
faultState
Element
faultState
I3P
V3P
I3P
PICKUP
TRIP
ANSI05000740 V1 EN
Figure 32: Functional overview of OC4PTOC (51/67)
The sampled analog phase currents are processed in a pre-processing function block.
Using a parameter setting MeasType within the general settings for the four step phase
Section 7 1MRK 505 277-UUS C
Current protection
78
Technical Manual