Name Values (Range) Unit Step Default Description
FunType9 0 - 255 - 1 0 Function type for analog channel 9
(IEC-60870-5-103)
InfNo9 0 - 255 - 1 0 Information number for analog channel 9
(IEC-60870-5-103)
FunType10 0 - 255 - 1 0 Function type for analog channel 10
(IEC-60870-5-103)
InfNo10 0 - 255 - 1 0 Information number for analog channel10
(IEC-60870-5-103)
Table 220: A1RADR Non group settings (advanced)
Name Values (Range) Unit Step Default Description
NomValue01 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 1
UnderTrigOp01 Disabled
Enabled
- - Disabled Use under level trigger for analog channel 1
(on) or not (off)
UnderTrigLe01 0 - 200 % 1 50 Under trigger level for analog channel 1 in %
of signal
OverTrigOp01 Disabled
Enabled
- - Disabled Use over level trigger for analog channel 1
(on) or not (off)
OverTrigLe01 0 - 5000 % 1 200 Over trigger level for analog channel 1 in % of
signal
NomValue02 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 2
UnderTrigOp02 Disabled
Enabled
- - Disabled Use under level trigger for analog channel 2
(on) or not (off)
UnderTrigLe02 0 - 200 % 1 50 Under trigger level for analog channel 2 in %
of signal
OverTrigOp02 Disabled
Enabled
- - Disabled Use over level trigger for analog channel 2
(on) or not (off)
OverTrigLe02 0 - 5000 % 1 200 Over trigger level for analog channel 2 in % of
signal
NomValue03 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 3
UnderTrigOp03 Disabled
Enabled
- - Disabled Use under level trigger for analog channel 3
(on) or not (off)
UnderTrigLe03 0 - 200 % 1 50 Under trigger level for analog channel 3 in %
of signal
OverTrigOp03 Disabled
Enabled
- - Disabled Use over level trigger for analog channel 3
(on) or not (off)
OverTrigLe03 0 - 5000 % 1 200 Overtrigger level for analog channel 3 in % of
signal
NomValue04 0.0 - 999999.9 - 0.1 0.0 Nominal value for analog channel 4
UnderTrigOp04 Disabled
Enabled
- - Disabled Use under level trigger for analog channel 4
(on) or not (off)
UnderTrigLe04 0 - 200 % 1 50 Under trigger level for analog channel 4 in %
of signal
Table continues on next page
Section 12 1MRK 505 277-UUS C
Monitoring
260
Technical Manual