Table 346: SMAI_20_1 Non group settings (advanced)
Name Values (Range) Unit Step Default Description
Negation Disabled
NegateN
Negate3Ph
Negate3Ph+N
- - Disabled Negation
MinValFreqMeas 5 - 200 % 1 10 Limit for frequency calculation in % of VBase
Even if the AnalogInputType setting of a SMAI block is set to Current,
the MinValFreqMeas setting is still visible. This means that the
minimum level for current amplitude is based on VBase. For example,
if VBase is 20000, the minimum amplitude for current is 20000 * 10%
= 2000. This has practical affect only if the current measuring SMAI is
used as a frequency reference for the adaptive DFT. This is not
recommended, see the Setting guidelines.
Table 347: SMAI_20_12 Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global Base Value
groups
DFTReference InternalDFTRef
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
- - InternalDFTRef DFT reference
ConnectionType Ph-N
Ph-Ph
- - Ph-N Input connection type
AnalogInputType Voltage
Current
- - Voltage Analog input signal type
Table 348: SMAI_20_12 Non group settings (advanced)
Name
Values (Range) Unit Step Default Description
Negation Disabled
NegateN
Negate3Ph
Negate3Ph+N
- - Disabled Negation
MinValFreqMeas 5 - 200 % 1 10 Limit for frequency calculation in % of VBase
Section 15 1MRK 505 277-UUS C
Basic IED functions
402
Technical Manual