Retrieve an existing ASAP
...................................................................................................................................................................................................................................
When to use
This procedure is used to retrieve information about one or more existing alarm
severity assignment profile(s).
Before you begin
Before performing this task, you must have an overview of the network topology.
1. Log into the ITM
®
CIT, and
2. Connect to the NE.
Required equipment
The following equipment is required to perform this task:
• ITM
®
CIT
Procedure
Follow this procedure to retrieve parameter values for an ASAP:
...................................................................................................................................................................................................
1
Select Alarms → ASAP List.
Result: The Alarm Severity Assignment Profiles List window is displayed.
...................................................................................................................................................................................................
2
Select the ASAP to be retrieved in the ASAP List, then click on Details.
Result: The Alarm Severity Assignment Profile Information window is displayed
for the selected ASAP.
...................................................................................................................................................................................................
3
As an option, you can store the currently displayed list:
If { then {
you want to store the list as a
standard text file (ASCII format)
click the
Report button and specify a filename and
a destination.
...................................................................................................................................................................................................
4
Click on Close to close the window.
E ND OF STEPS
...................................................................................................................................................................................................
Alarm management
...................................................................................................................................................................................................................................
6-38
Alcatel-Lucent - Proprietary
See notice on first page
365-312-807R7.2
Issue 4, May 2007