Rockwell Automation Publication 750-IN001P-EN-P - April 2017 223
Power Wiring Chapter 4
Figure 127 - Drive Assembly PE-A1 MOV and PE-A2 Input Filter Caps Jumper Location
When the PE-A1 jumper wire is connected, use this torque and tool:
Recommended torque = 1.8 N•m (16.0 lb•in)
Recommended screwdriver = T20 Hexalobular
DisconnectedConnected
PE-A1 and GND positions on early production drives.
DisconnectedConnected
IMPORTANT PE-A1 and PE-A2 jumper are only used by three-phase input drive
assemblies and are not applicable to common DC input drives assemblies.