284 Rockwell Automation Publication 750-IN001P-EN-P - April 2017
Chapter 5 I/O Wiring
20-COMM Carrier
Enables use of some 20-COMM adapters with PowerFlex 750-Series drives.
See Table 106
.
See publication 750COM-IN001
for instructions on how to install a 20-
COMM adapter on the 20-COMM Carrier.
Table 106 - 20-COMM-x Network Adapter Compatibility with 750-Series Drives
Frame 1 Drives Installation Recommendations
PowerFlex Frame 1 drives require the use of the communication carrier kit,
catalog number 20-750-20COMM-F1. This kit contains the required adapter
plate.
Only install the communication carrier kit in Port 4. See page 252
for port
locations. Port 5 is not accessible when this module is installed.
Frame 2 and Larger Drives Installation Recommendations
We recommend that you install the 20-750-20COMM Communication
Carrier in Port 6. Installing the communication carrier in Port 4 or Port 5
makes the adjacent left port inaccessible to other option modules, and can
interfere with network cable connections.
20-750-20COMM-F1
20-750-20COMM
Frame 1
Frames 2 and Larger
Adapter Accesses Ports 0…6
for I/O Connections
(Implicit and Explicit
Messaging)
Accesses Ports 7
and Higher
(I/O,
Explicit
Messaging)
Supports Drive
Add-on Profiles
Supports Asian
Languages
(6)
(6) Chinese, Japanese, and Korean languages are supported at the time of publication.
Cat. No. Type
20-COMM-B BACnet MS/TP
Not Compatible
20-COMM-C ControlNet
(Coax)
v3.001
(4)
v3.001
(4)
(4) Requires this adapter firmware revision or higher.
(5)
(5) Requires firmware revision v1.05 or higher of the drive Add-on Profiles for RSLogix 5000® version v16 or higher.
v3.001
(4)
20-COMM-D DeviceNet
(2)
(2) Controller must be able to read/write 32-bit floating point (REAL) values.
Not Compatible
20-COMM-E EtherNet/IP v4.001
(4)
v4.001
(4) (5)
v4.001
(4)
20-COMM-H RS-485 HVAC v2.009
(3)(4)
(3) Supports all three modes of operation (RTU, P1, N2).
Not Compatible
20-COMM-K CANopen v1.001
(4)
20-COMM-L LonWorks v1.007
(4)
20-COMM-M Modbus/TCP v2.001
(4)
v2.001
(4)
Not Compatible v2.001
(4)
20-COMM-P ControlNet
(Fiber)
v1.006
(4)
v1.006
(4)
Not Compatible
20-COMM-Q PROFIBUS DP v3.001
(4)
v3.001
(4) (5)
v3.001
(4)
20-COMM-R
(1)
(1) This item has End of Life status.
Remote I/O
(2)
Not Compatible
20-COMM-S RS-485 DF1
(2)