Page #116 background imageLoading...
Page #116 background image
5-26 BESTCOMS Software DECS-200
Data Logging Setup, Data Logging Enable.
Enables and disables data logging.
Data Logging Setup, Pre-Trigger Points.
Selects the number of data points that are recorded prior to a
data log being triggered. A setting of 0 to 599 may be entered in increments of 1.
Data Logging Setup, Post Trigger Points.
Displays the number of data points that are recorded after a
data log is triggered. The value of this read-only field is determined by the Pre-Trigger Points and Sample
Interval settings.
Data Logging Setup, Sample Interval.
Establishes the sample rate of the data points. When the Generator
Frequency setting (System Configuration screen, System Options tab) is 60 hertz, a sample interval of
0.016 to 10 seconds may be selected from the pull-down menu. When the Generator Frequency setting is
50 hertz, a sample interval of 0.004 to 10 seconds may be selected from the pull-down menu.
Data Logging Setup, Pre-Trig Duration.
Displays the length of time that pre-trigger data points are
recorded. The value of this read-only field is determined by the Pre-Trigger Points and Sample Interval
settings.
Data Logging Setup, Post Trig Duration.
Displays the length of time that post-trigger data points are
recorded. The value of this read-only field is determined by the Pre-Trigger Points and Sample Interval
settings.
Data Logging Setup, Total Log Duration.
Displays the total recording time for a data log and equals the
sum of the values in the Pre-Trig Duration and Post Trig Duration fields. The value of this read-only field
is determined by the Pre-Trigger Points and Sample Interval settings.
View Sequence Of Events Reporting.
Clicking this button displays the Sequence of Events Reporting
screen (Figure 5-30). Sequence of Events Reporting screen displays and controls are described in the
following paragraphs.
Figure 5-30. Sequence of Event Reporting
Report Summary.
This area of the Sequence of Event Recording screen lists the available sequence of
events records. The records displayed are determined by the selection made in the Display the Following
Events setting area.
Event List.
This area of the Sequence of Event Recording screen lists the available sequence of events
records. The records displayed are determined by the selection made in the Display the Following Events
setting area.
Reset New Event List.
Clicking this button clears all new events from the Event List.
Display the Following Events.
The event type displayed in the Event List is controlled by selection made
here. Available event-type selections are New, All New and Old, New Alarm, New I/O, and New Mode.
Print/Save Report.
Clicking this button allows the report to be saved as a text file or printed.