DECS-200 Human-Machine Interface 2-7
Ref. Parameter Minimum Maximum Increment Default
No Voltage Sensing On, Off N/A Off
7.5.3 Setpoint at Low Limit On, Off N/A Off
Setpoint at High Limit On, Off N/A Off
System Below 10 Hz On, Off N/A Off
Open Exciter Diode On, Off N/A Off
Shorted Exciter Diode On, Off N/A Off
7.5.4 Relay 2 Contact Sense NC, NO N/A NO
Relay 2 Annunc. Type Momentary Maintained, Latched N/A Maintained
Relay 2 Moment Time 0.10 s 5.00 s 50 ms 0.10 s
Field Overvoltage On, Off N/A Off
Stator Undervoltage On, Off N/A Off
7.5.5 Stator Overvoltage On, Off N/A Off
Underfrequency On, Off N/A Off
Overexcitation On, Off N/A Off
Underexcitation On, Off N/A Off
FCR Mode On, Off N/A Off
No Voltage Sensing On, Off N/A Off
7.5.6 Setpoint at Low Limit On, Off N/A Off
Setpoint at High Limit On, Off N/A Off
System Below 10 Hz On, Off N/A Off
Open Exciter Diode On, Off N/A Off
Shorted Exciter Diode On, Off N/A Off
7.5.7 Relay 3 Contact Sense NC, NO N/A NO
Relay 3 Annunc. Type Momentary, Maintained, Latched N/A Maintained
Relay 3 Moment Time 0.10 s 5.00 s 50 ms 0.10 s
Field Overvoltage On, Off N/A Off
Field Overcurrent On, Off N/A Off
Stator Undervoltage On, Off N/A Off
7.5.8 Stator Overvoltage On, Off N/A Off
Underfrequency On, Off N/A Off
Overexcitation Limit On, Off N/A Off
Underexcitation Limit On, Off N/A Off
FCR Mode On, Off N/A Off
No Voltage Sensing On, Off N/A Off
7.5.9 Setpoint at Low Limit On, Off N/A Off
Setpoint at High Limit On, Off N/A Off
System Below 10 Hz On, Off N/A Off
Open Exciter Diode On, Off N/A Off
Shorted Exciter Diode On, Off N/A Off
7.6.1 AVR Traverse Rate 10 s 200 s 1 s 20 s
FCR Traverse Rate 10 s 200 s 1 s 20 s
Var Traverse Rate 10 s 200 s 1 s 20 s
PF Traverse Rate 10 s 200 s 1 s 20 s
7.7.1 AVR Prep Mode Maintain, Release N/A Release
FCR Prep Mode Maintain, Release N/A Release
Var Prep Mode Maintain, Release N/A Release
PF Prep Mode Maintain, Release N/A Release
7.8.1 Soft Start Level 0% 90% 1% 5%
Soft Start Time 1 s 7,200 s 1 s 5 s
7.9.1 Internal Track rate 1.0 s 80 s 0.1 s 20.0 s