Configuration Mode (ConF)
183
Code Nam e / De s cription Adjustment range Factory setting
JPF

[Skip Frequency]
0 to 599 Hz 0 Hz
Skip frequency. This parameter helps to prevent prolonged operation within an adjustable range around the regulated frequency.
This function can be used to help to prevent a critical speed, w hich would cause resonance, being reached. Setting the function
to 0 renders it inactive.
JF2

[Skip Frequency 2]
0 to 599 Hz 0 Hz
2nd skip frequency. This parameter helps to prevent prolonged operation w ithin an adjustable range around the regulated
frequency. This function can be used to help to prevent a critical speed, w hich would cause resonance, being reached. Setting
the function to 0 renders it inactive.
JF3

[3rd Skip Frequency]
0 to 599 Hz 0 Hz
3rd skip frequency. This parameter helps to prevent prolonged operation w ithin an adjustable range around the regulated
frequency. This function can be used to help to prevent a critical speed, w hich would cause resonance, being reached. Setting
the function to 0 renders it inactive.
JFH
*

[Skip.Freq.Hysteresis]
0.1 to 10 Hz 1 Hz
This parameter is visible if at least one skip frequency
[Sk ip Fre que ncy]
(JPF),
[Sk ip Freque ncy 2]
(JF2) or
[3rd Sk ip Freque ncy]
(JF3) is different from 0.
Skip frequency range: betw een
(JPF
JFH)
and
(JPF
+
JFH),
for example.
This adjustment is common to the 3 frequencies
(JPF, JF2, JF3).
(1) The parameter can also be accessed in the
[SETTINGS]
(SEt-)
menu.
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from w ithin the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
Parameter that can be modified during operation or w hen stopped.
*