Configuration Mode (ConF)
PRESET SPEEDS
2, 4, 8 or 16 s peeds can be pres et, requiring 1, 2, 3 or 4 logic inputs res pectively.
Note:
You m us t configure 2 and 4 s peeds in order to obtain 4 speeds.
You m us t configure 2, 4 and 8 speeds in order to obtain 8 speeds .
You m us t configure 2, 4, 8, and 16 speeds in order to obtain 16 s peeds .
Com bination table for pres et speed inputs
16 s peeds
LI (PS16)
8 s peeds
LI (PS8)
4 s peeds
LI (PS4)
2 s peeds
LI (PS2)
Spe ed reference
0
0
0
0
Reference (1)
0
0
0
1
SP2
0
0
1
1
0
1
SP3
SP4
0
0
0
1
1
1
1
0
0
1
1
0
1
0
1
SP5
SP6
SP7
SP8
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
SP9
SP10
SP11
SP12
SP13
SP14
SP15
SP16
(1) See the diagram on page 147: Reference 1 = (SP1).
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > FUN- > PSS-