Configuration Mode (ConF)
Full
Code Nam e / De s cription Adjustment range
Factory setting
tCC
[2/3 wire control]
[2 w ire]
(2C)
2 s
WARNING
UNANTICIPATED EQUIPMENT OPERATION
If this param eter is changed, the param eters
[Reverse
a
ssign.]
(
rr
S
) and
[2
wire type]
(
tC
t
) and the
ass ignm ents of the digital inputs are res et to the factory setting.
Verify that this change is com patible with the type of wiring us ed.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
See
[2/3 w ire control]
(tCC) page 125.
[2 w ire]
(2C)
2-
w ire control (level commands):
This is the input state (0 or 1) or edge (0 to 1 or 1 to 0), w hich controls running or stopping.
Example of "source" w iring:
+24 LI1 LIx
LI1: forward
LIx: reverse
[3 w ire]
(3C)
3-
w ire control (pulse commands):
A "forward" or "reverse" pulse is sufficient to command starting, a "stop" pulse is sufficient
to command stopping.
Example of "source" w iring:
+24 LI1 LI2 LIx
LI1: stop
LI2: forward
LIx: reverse
2C
3C
CFG
[Macro configuration]
[Start/Stop]
(StS)
*
WARNING
UNANTICIPATED EQUIPMENT OPERATION
Verify that the selected m acro configuration is com patible with the type of wiring used.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
See
[M acro configuration]
(CFG) page 82.
[Start/Stop]
(StS): Start/stop
[M . handling]
(HdG): Handling
[Hois t ing]
(
HS
t
):
Hoisting
[Gen. Us e ]
(GEn): General use
[PID re gul.]
(PId):
PID regulation
[Net wo rk
C.]
(
nE
t
):
Communic at ion
bus
2 s
StS
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > SIM-