Configuration Mode (ConF)
Code Nam e / De s cription Adjustment range
Factory setting
CCFG
[Customized macro]
Read-only parameter, only visible if at least one macro configuration parameter has been modified.
nO
[No]
(nO): No
bFr
[Standard mot. freq]
[50Hz IEC]
(50)
50
This parameter modifies the presets of the follow ing parameters:
[Rated m otor volt.]
(UnS) below ,
[High s pe e d]
(HSP) page
87,
[Freq .
thres h old ]
(
Ftd
)
page
102,
[Rate d
motor
freq.]
(
FrS
)
and
[Max
freque nc y ]
(
tFr
)
.
[50Hz IEC]
(50): Drive 50 Hz
[60Hz NEM A]
( 0): Drive 60 Hz
IPL
[Input phase loss]
Yes or No, according to drive
rating
*
This parameter is only accessible in this menu on 3-phase drives.
If one phase disappears, the drive sw itches to fault mode
[Input phas e loss]
(PHF), but if 2 or 3 phases disappear, the drive
continues to operate until it trips on an undervoltage detected fault (the drive trips in
[Input phase los s]
(PHF) if there is an
input phase loss and if this leads to performance decrease).
See
[Input phas e loss]
(IPL)
page 256.
[Ignore]
(nO): Detected fault ignored, to be used w hen the drive is supplied via a single-phase supply or by the DC bus
[Freewheel]
(YES): With freewheel stop
nO
nPr
*
[Rated motor power]
According to drive rating
Rated motor pow er given on the nameplate, in kW if
[Standard m ot. fre q]
(bFr)
is set to
[50Hz IEC]
(50), in HP if
[Standard m ot. fre q]
(bFr)
is set to
[60Hz NEM A]
( 0).
See
[Rated m otor pow er]
(nPr)
page 107.
UnS
*
[Rated motor volt.]
100 to 480 V According to drive rating
Rated motor voltage given on the nameplate.
ER24-…K/B: 100 to 240 V – ER24-…/4K/B: 200 to 480 V.
See
[Rated m otor volt.]
(UnS) page 107.
nCr
*
[Rated mot. current]
0.25 to 1.5 In (1) According to drive rating and
[Standa rd
mot.
freq]
(
bF
r
)
Rated motor current given on the nameplate.
See
[Rated m ot. current]
(nCr)
page 107.
FrS
*
[Rated motor freq.]
10 to 800 Hz 50 Hz
Rated motor frequency given on the nameplate.
The factory setting is 50 Hz, or preset to 60 Hz if
[Standard m ot. freq]
(bFr)
is set to 60 Hz.
This
paramete r
is
not
visible
if
[Motor
control
type]
(
Ctt
)
page
105
is
set
to
[Sync .
mot.]
(
SYn
).
See
[Rated m otor freq.]
(FrS)
page 107.
nSP
*
[Rated motor speed]
0 to 65,535 rpm According to drive rating
Rated motor speed given on the nameplate.
This
paramete r
is
not
visible
if
[Motor
control
type]
(
Ctt
)
page
105
is
set
to
[Sync .
mot.]
(
SYn
).
See
[Rated m otor s peed]
(nSP) page 107.
0 to 9,999 rpm then 10.00 to 60.00 krpm on the integrated display terminal.
If, rather than the rated speed, the nameplate indicates the synchronous speed and the slip in Hz or as a %, calculate the rated
speed as follow s:
100 - slip as a %
Nominal speed = Synchronous speed x
100
or
50 - slip in Hz
Nominal speed = Synchronous speed x (50 Hz motors)
50
or
Nominal speed = Synchronous speed x
60 - slip in Hz
(60 Hz motors)
60
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > SIM-