Configuration Mode (ConF)
221
Code Nam e / De s cription Adjustment range Factory setting
FUn
-
[APPLICATION FUNCT.]
(continued)
LLC
-
[LINE CONTACTOR COMMAND]
LLC
nO
LO1
r2
dO1
[Line contactor ass.]
[No]
(nO)
Logic output or control relay.
[No]
(nO): Function not assigned (in this case, none of the function parameters can be accessed)
[LO1]
(LO1): Logical output LO1
[R2]
(r2):
Relay r2
[d01]
(dO1): Analog output AO1 functioning as a logic output. Selection can be made if
[AO1 as s ignment]
(AO1) page 144
is set to
[No]
(nO)
LES
*
nO
LI1
...
[Drive lock]
[No]
(nO)
This parameter can be accessed if
[Line contactor as s .]
(
LLC
) is not set to
[No]
(
nO
).
The drive locks w hen the assigned input or bit changes to 0.
[No]
(nO): Function inactive
[LI1]
(LI1):
Logical input LI1
[...]
(...): See the assignment conditions on page 153
LC
t
*
[Mains V. time out]
5 to 999 s 5 s
Monitoring time for closing of line contactor. If, once this time has elapsed, there is no voltage on the drive pow er circuit, the
drive w ill lock w ith a
[Line contactor]
(
LCF
) detected fault.
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from w ithin the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
*