Configuration Mode (ConF)
Code Nam e / De s cription Adjustment range Factory setting
UdL
*
nO
YES
FSt
[Underload Managmt.]
[Freew heel]
(YES)
Behavior on sw itching to underload detection.
[Ignore ]
(nO): Detected fault ignored
[Freew heel]
(YES): Freew heel stop
[Ram p s top]
(rMP): Stop on ramp
[Fast s top]
(FSt): Fast stop
FtU
*
[Underload T.B. Rest.]
0 to 6 min 0 min
This parameter cannot be accessed if
[Unde rload M angm t.]
(UdL) is set to
[Ignore ]
(nO).
Minimum time permitted betw een an underload being detected and any automatic restart.
In
order
to
allow
an
automatic
restart,
the
value
of
[Max.
resta rt
time]
(
tAr
)
page
252
must
exceed
this
paramet er
by
at
least
one minute.
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from w ithin the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
Parameter that can be modified during operation or w hen stopped.
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > FLT - > ULD-
*