Configuration Mode (ConF)
Code Nam e / De s cription Adjustment range Factory setting
CL2
*
[I Limit. 2 value]
0 to 1.5 In (1) 1.5 In (1)
NOTICE
OVERHEATING AND DAMAGE TO THE MOTOR
•
Verify that the m otor is properly rated for the maxim um current to be applied to the m otor.
•
Cons ider the duty cycle of the m otor and all factors of your application including derating requirements in
determ ining the current lim it.
Failure to follow these instructions can result in equipment damage.
See page 218.
Note:
If the setting is less than 0.25 In, the drive may lock in
[Output Phas e Loss]
(OPL) fault mode if this has been enabled
(see page 256). If it is less than the no-load motor current, the motor cannot run.
FLU
[Motor fluxing]
[No]
(FnO)
*
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
If the param eter
[Motor fluxing]
(
FL
U
) is s et to
[
C
ontinuou
s]
(
FC
t
), fluxing is always active, even if the
m otor does not run.
•
Verify that us ing this s etting does not res ult in uns afe conditions.
Failure to follow these instructions will result in death or serious injury.
NOTICE
OVERHEATING AND DAMAGE TO THE MOTOR
Verify that the connected m otor is properly rated for the flux current to be applied in order to avoid overheating
and dam age to the m otor.
Failure to follow these instructions can result in equipment damage.
The
paramet er
is
visible
if
[Mot o r
control
type]
(
Ctt
)
page
105
is
not
set
to
[Sync .
mot.]
(
SYn
).
In order to obtain rapid high torque on startup, magnetic flux needs to already have been established in the motor.
In
[Cont in u o u s]
(
FC
t
)
mode,
the
drive
automatic ally
builds
up
flux
when
it
is
powered
up.
In
[Not cont.]
(FnC) mode, fluxing occurs w hen the motor starts up.
The flux current is greater than
[Rated m ot. current]
(nCr)
w hen the flux is established and is then adjusted to the motor
magnetizing current. See page 189.
[Not cont.]
(FnC): Non-continuous mode
[Continuous ]
(FCt):
Continuous mode. This option is not possible if
[Auto DC inje ction]
(AdC) page 176 is
[Ye s ]
(YES)
or
if
[Type
of
stop]
(
Stt
)
page
173
is
[Free w h e e l]
(
nSt
).
[No]
(FnO): Function inactive. This option is not possible if
[Brak e as s ignm e nt]
(bLC) page 194 is not
[No]
(nO).
2 s
FnC
FnO
tLS
[Low speed time out]
0 to 999.9 s 0 s
Maximum operating time at
[Low spe e d]
(LSP) (see page 87).
Follow ing operation at LSP for a defined period, a motor stop is requested automatically. The motor w ill restart if the reference
is greater than LSP and if a run command is still present. See page 213.
Note:
A value of 0 indicates an unlimited period of time.
Note:
If
[Low
spee d
time
out]
(
tLS
)
is
not
0,
[Type
of
stop]
(
St
t
)
page
173
is
forced
to
[Ra mp
stop]
(
rM
P
)
(only
if
a
ramp stop can be configured).
JGF
*
[Jog frequency]
0 to 10 Hz 10 Hz
Reference in jog operation. See page 178.
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > SET-