CG Drives & Automation,01-5326-01r5 169
AnIn1 Function Min [5134]
With AnIn1 Function Min the physical minimum value is
scaled to selected process unit. The default scaling is
dependent of the selected function of AnIn1 [511].
Table 36 shows corresponding values for the min and max
selections depending on the function of the analogue input
[511].
Communication information
AnIn1 Function Value Min [5135]
With AnIn1 Function ValMin you define a user-defined
value for the signal. Only visible when user-defined is
selected in menu [5134].
Communication information
AnIn1 Function Max [5136]
With AnIn1 Function Max the physical maximum value is
scaled to selected process unit. The default scaling is
dependent of the selected function of AnIn1 [511]. See
Table 36.
Communication information
AnIn1 Function Value Max [5137]
With AnIn1 Function VaMax you define a user-defined
value for the signal. Only visible when user-defined is
selected in menu [5136].
Communication information
Example:
Process sensor is a sensor with the following specification:
Range: 0–3 bar
Output: 2–10 mA
Analogue input should be set up according to:
[512] AnIn1 Setup = User mA
[5131] AnIn1 Min = 2 mA
[5132] AnIn1 Max = 10 mA
[5134] AnIn1 Function Min = User-defined
[5135] AnIn1 VaMin = 0.000 bar
[5136] AnIn 1 Function Max = User-defined
[5137] AnIn1 VaMax = 3.000 bar
5134 AnIn1 FcMin
Default: Min
Min 0 Min value
Max 1 Max value
User-
defined
2 Define user value in menu [5135]
Ta b l e 3 6
AnIn Function Min Max
Speed Min Speed [341] Max Speed [343]
Torque 0% Max Torque [351]
Process Ref Process Min [324] Process Max [325]
Process Value Process Min [324] Process Max [325]
Modbus Instance no/DeviceNet no: 43206
Profibus slot/index 169/110
EtherCAT and CANopen index (hex) 4c86
Profinet IO index 19590
Fieldbus format UInt
Modbus format UInt
5135 AnIn1 VaMin
Default: 0.000
Range: -10000.000 – 10000.000
Modbus Instance no/DeviceNet no: 43541
Profibus slot/index 170/190
EtherCAT and CANopen index (hex) 4dd5
Profinet IO index 19925
Fieldbus format
Long, 1=1 rpm, 1 %, 1°
or 0.001 if Process Value/
Process Ref using a [322]
unit
Modbus format EInt
5136 AnIn1 FcMax
Default: Max
Min 0 Min value
Max 1 Max value
User-
defined
2 Define user value in menu [5137]
Modbus Instance no/DeviceNet no: 43207
Profibus slot/index 169/111
EtherCAT and CANopen index (hex) 4c87
Profinet IO index 19591
Fieldbus format UInt
Modbus format UInt
5137 AnIn1 VaMax
Default: 0.000
Range: -10000.000 – 10000.000
Modbus Instance no/DeviceNet no: 43551
Profibus slot/index 170/200
EtherCAT and CANopen index (hex) 4ddf
Profinet IO index 19935
Fieldbus format
Long, 1=1 rpm, 1 %, 1°
or 0.001 if Process Value/
Process Ref using a [322]
unit
Modbus format EInt
NOTE: With AnIn Min, AnIn Max, AnIn Function Min
and AnIn Function Max settings, loss of feedback
signals (e.g. voltage drop due to long sensor wiring)
can be compensated to ensure an accurate process
control.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CG Emotron VFX Series and is the answer not in the manual?

CG Emotron VFX Series Specifications

General IconGeneral
BrandCG
ModelEmotron VFX Series
CategoryController
LanguageEnglish

Related product manuals