256
Binary output: Speed Up
Related
applications
All
Description
This output together with the complementary output Speed Down is
designed for speed and power control at gen-sets, where the governor does
not support analog control. The outputs are also used for direct control of a
gas throttle at asynchronous gen-sets.
NOTE:
Droop function is required when these outputs are used for power control
through a governor.
Binary output: Speed Down
Related
applications
All
Description
This output together with the complementary output Speed Up is designed
for speed and power control at gen-sets, where the governor does not
support analog control. The outputs are also used for direct control of a gas
throttle at asynchronous gen-sets.
NOTE:
Droop function is required when these outputs are used for power control
through a governor.
Binary output: AVR Up
Related
applications
All
Description
This output together with the complementary output AVR Down is designed
for voltage and power factor control at gen-sets, where the AVR does not
support analog control.
NOTE:
Droop function is required when these outputs are used for power factor
control.
Binary output: AVR Down
Related
applications
All
Description
This output together with the complementary output AVR Up is designed for
voltage and power factor control at gen-sets, where the AVR does not
support analog control.
NOTE:
Droop function is required when these outputs are used for power factor
control.