InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
This output together with the complementary output Speed Down is
designed for speed and power control at gen-sets, where the governor does
not support analog control. The outputs are also used for direct control of a
gas throttle at asynchronous gen-sets.
NOTE:
Droop function is required when these outputs are used for power control
through a governor.
Binary output: Speed Down
This output together with the complementary output Speed Up is designed
for speed and power control at gen-sets, where the governor does not
support analog control. The outputs are also used for direct control of a gas
throttle at asynchronous gen-sets.
NOTE:
Droop function is required when these outputs are used for power control
through a governor.
This output together with the complementary output AVR Down is designed
for voltage and power factor control at gen-sets, where the AVR does not
support analog control.
NOTE:
Droop function is required when these outputs are used for power factor
control.
This output together with the complementary output AVR Up is designed for
voltage and power factor control at gen-sets, where the AVR does not
support analog control.
NOTE:
Droop function is required when these outputs are used for power factor
control.