EasyManuals Logo

ComAp InteliCompact NT Reference Guide

ComAp InteliCompact NT
291 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #289 background imageLoading...
Page #289 background image
InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
289
Alarm: Earth Fault Current
Alarm type
Shutdown
Alarmlist
message
SdEarthFltCurr
Alarm evaluated
All the time
Related
applications
All
Description
This alarm indicates that the value of earth current EarthFaultCurr is higher
than the setpoint EarthFault Sd and EarthFaulth Del delay has elapsed. The
alarm activates binary output AL Earth Fault.
Alarm: Excitation Lost
Alarm type
Breaker open & cool down
Alarmlist
message
BOC ExctLoss
Alarm evaluated
All the time
Related
applications
All
Description
Loss of excitation is based on measurement of negative kVAr. This alarm
indicates that the value of negative kVAr is higher than the setpoint
ExcitationLoss and ExctLoss Del delay has elapsed. This alarm activates AL
Exct Loss binary output.
Alarm: Override
Alarm type
Shutdown
Alarmlist
message
Sd Override
Alarm evaluated
All the time
Related
applications
All
Description
This alarm occurs when binary input Sd Override is activated.
Alarm: IOM Fail
Alarm type
Shutdown
Alarmlist
message
Sd IOM Fail
Alarm evaluated
All the time
Related
applications
All
Description
Communication error between the controller and extension module IG-IOM
or IGS-PTM.
Alarm: RA Fail
Alarm type
Warning

Table of Contents

Other manuals for ComAp InteliCompact NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliCompact NT and is the answer not in the manual?

ComAp InteliCompact NT Specifications

General IconGeneral
BrandComAp
ModelInteliCompact NT
CategoryController
LanguageEnglish

Related product manuals