InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp May 2015
289
Alarm: Earth Fault Current
Alarm type
Shutdown
Alarmlist
message
SdEarthFltCurr
Alarm evaluated
All the time
Related
applications
All
Description
This alarm indicates that the value of earth current EarthFaultCurr is higher
than the setpoint EarthFault Sd and EarthFaulth Del delay has elapsed. The
alarm activates binary output AL Earth Fault.
Alarm: Excitation Lost
Alarm type
Breaker open & cool down
Alarmlist
message
BOC ExctLoss
Alarm evaluated
All the time
Related
applications
All
Description
Loss of excitation is based on measurement of negative kVAr. This alarm
indicates that the value of negative kVAr is higher than the setpoint
ExcitationLoss and ExctLoss Del delay has elapsed. This alarm activates AL
Exct Loss binary output.
Alarm: Override
Alarm type
Shutdown
Alarmlist
message
Sd Override
Alarm evaluated
All the time
Related
applications
All
Description
This alarm occurs when binary input Sd Override is activated.
Alarm: IOM Fail
Alarm type
Shutdown
Alarmlist
message
Sd IOM Fail
Alarm evaluated
All the time
Related
applications
All
Description
Communication error between the controller and extension module IG-IOM
or IGS-PTM.
Alarm: RA Fail
Alarm type
Warning