Chapter 4 Parameters|
4-68 Revision Jan. 2009, 06EE, SW--PW V1.12/CTL V2.12
This parameter determinates the constant speed When Pr.02.08 is set to 2 or 3.
02.11 Keypad Frequency Command Unit: 0.01
Settings 0.00 to 600.0Hz Factory Setting: 60.00
This parameter can be used to set frequency command or read keypad frequency command.
Related parameters: Pr.02.12 (Communication Frequency Command)
02.12 Communication Frequency Command Unit: 0.01
Settings 0.00 to 600.0Hz Factory Setting: 60.00
This parameter can be used to set frequency command or read communication frequency
command.
It can use this parameter for remote control via communication.
02.13
The Selections for Saving Keypad or Communication Frequency
Command
Factory Setting: 0
Settings 0 Save Keypad & Communication Frequency
1 Save Keypad Frequency only
2 Save Communication Frequency only (Not for VFD*E*C model)
This parameter is used to save keypad or RS-485 frequency command.
Setting 0: After the AC motor drive is power off, save keypad and communication frequency in
the AC motor drive.
Setting 1: After the AC motor drive is power off, only save keypad frequency in the AC motor
drive and won’t save communication frequency.
Setting 2: After the AC motor drive is power off, only save communication frequency in the AC
motor drive and won’t save keypad frequency.
The keypad or communication frequency only can be saved when Pr. 02.00/Pr.02.09=0 (the
source of frequency is from keypad) or Pr.02.00/Pr.02.09=3(the source of frequency is from
communication).
Related parameters: Pr.02.00(Source of First Master Frequency Command) and
Pr.02.09(Source of Second Frequency Command).