Chapter 4 Parameters|
Revision Jan. 2009, 06EE, SW--PW V1.12/CTL V2.12 4-109
Related parameters: Pr.01.09(Accel Time 1), Pr.01.11(Accel Time 2), Pr.01.16(Auto
acceleration / deceleration (refer to Accel/Decel time setting)), Pr.03.00(Multi-function Output
Relay (RA1, RB1, RC1)), Pr.03.01(Multi-function Output Terminal MO1) and Pr.06.03(Over-
Torque Detection Mode (OL2))
06.01
Over-Current
Detection
Level
Over-Current Stall
prevention during
Acceleration,
frequency held
output current
setting
frequency
previous acceleration time
actual acceleration time when over-current stall
prevention is enabled
output current
Time
06.02
Over-current Stall Prevention during Operation
Unit: 1
Settings 20 to 250% Factory Setting: 170
0: disable
The over-current stall prevention during operation function is a protection. When the motor
runs with constant speed, the AC motor drive will decrease the output frequency automatically
when momentary overload.
If the output current exceeds the setting specified in Pr.06.02 when the drive is operating, the
drive will decrease its output frequency by Pr.01.10/Pr.01.12 to prevent the motor stall. If the
output current is lower than (Pr.06.02 setting –rated current X 5%), the drive will accelerate
again by Pr.01.09/Pr.01.11 to catch up with the set frequency command value.
Related parameter: Pr.06.03 Over-Torque Detection Mode (OL2)