Chapter 4 Parameters|
4-156 Revision Jan. 2009, 06EE, SW--PW V1.12/CTL V2.12
This parameter is set to how to react when transmission errors occurs.
Setting 0: when transmission errors occur, it will display warning message “cEXX” on the
digital keypad and the motor will keep running. The warning message can be cleared after the
communication is normal.
Setting 1: when transmission errors occur, it will display warning message “cEXX” on the
digital keypad and the motor will stop by the deceleration time (Pr.01.10/01.12). It needs to
press “RESET” to clear the warning message.
Setting 2: When transmission errors occur, it will display warning message “cEXX” on the
digital keypad and the motor will free run to stop immediately. It needs to press “RESET” to
clear the warning message.
Setting 3: When transmission errors occur, it won’t display any warning message on the digital
keypad and the motor will still keep running.
See list of error messages below (see section 3.6 in Pr.09.04)
NOTE
The digital keypad is optional. Please refer to Appendix B for details. When using without this optional
keypad, the FAULT LED will be ON once there is error messages or warning messages from the
external terminals.
09.11 Time-out Detection for USB Card Unit: 0.1
Settings 0.0 to 120.0 sec Factory Setting: 0.0
0.0 Disable
09.12 COM port for PLC Communication (NOT for VFD*E*C models)
Factory Setting: 0
Settings 0
RS485
1 USB card