Chapter 4 Parameters|
4-44 Revision Jan. 2009, 06EE, SW--PW V1.12/CTL V2.12
the transient response of the AC motor drive.
Applications: textile equipment, press equipment, life equipment and drilling machine.
Related parameter: Pr.07.02 (Torque Compensation (Motor 0))
00.11
Reserved
00.12
50Hz Base Voltage Selection
Factory Setting: 0
Settings 0
230V/400V
1
220V/380V
This parameter determines the base voltage for 50Hz.
When Pr.00.02 is set to 9, the base voltage for 50Hz will set by Pr.00.12.
Related parameter: Pr.00.02 (Parameter Reset)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD-E and is the answer not in the manual?

Delta VFD-E Specifications

General IconGeneral
Protection FeaturesIP20
Enclosure RatingIP20
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Control ModeV/F, Sensorless Vector
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
Operating Temperature-10°C to +50°C
Analog Inputs2 (0-10V, 4-20mA)
Analog Outputs1 (0-10V)
Communication InterfaceRS-485
Output Voltage3-phase, equal to input voltage
Power Range0.4kW to 7.5 kW
Storage Temperature-20°C to +60°C
Humidity90% RH (non-condensing)
Cooling MethodFan cooled
Digital Outputs1 relay output