Chapter 4 Parameters|
4-22 Revision Jan. 2009, 06EE, SW--PW V1.12/CTL V2.12
Parameter Explanation Settings
Factory
Setting
Custome
r
08.01
DC Brake Time
during Start-Up
0.0 to 60.0 sec 0.0
08.02
DC Brake Time
during Stopping
0.0 to 60.0 sec 0.0
08.03
Start-Point for DC
Brake
0.00 to 600.0Hz 0.00
0: Operation stops after momentary power
loss
1: Operation continues after momentary
power loss, speed search starts with the
Last Frequency
08.04
Momentary Power
Loss Operation
Selection
2: Operation continues after momentary
power loss, speed search starts with the
minimum frequency
0
08.05
Maximum Allowable
Power Loss Time
0.1 to 20.0 sec 2.0
08.06
Base-block Speed
Search
0: Disable speed search
1: Speed search starts with last frequency
2: Starts with minimum output frequency
1
08.07
B.B. Time for Speed
Search
0.1 to 5.0 sec 0.5
08.08
Current Limit for
Speed Search
30 to 200% 150
08.09
Skip Frequency 1
Upper Limit
0.00 to 600.0 Hz 0.00
08.10
Skip Frequency 1
Lower Limit
0.00 to 600.0 Hz 0.00
08.11
Skip Frequency 2
Upper Limit
0.00 to 600.0 Hz 0.00
08.12
Skip Frequency 2
Lower Limit
0.00 to 600.0 Hz 0.00
08.13
Skip Frequency 3
Upper Limit
0.00 to 600.0 Hz 0.00
08.14
Skip Frequency 3
Lower Limit
0.00 to 600.0 Hz 0.00
08.15 Auto Restart After
Fault
0 to 10 (0=disable) 0