PROline Prosonic Flow 93 FOUNDATION Fieldbus 3 Transducer Blocks (transmission blocks)
Endress+Hauser 107
MODE_BLK AUTO - OOS Displays the current (Actual) and desired (Target) operating mode
of the relevant Transducer Block, the permitted modes (Permitted)
supported by the Transducer Block in question and the normal
operating mode (Normal).
Display:
AUTO
OOS
Note!
The Transducer Blocks support the following operating modes:
AUTO (automatic mode):
The block is executed.
OOS (out of service):
The block has the status "Out of Service". In the OOS
operating mode, the process variables are updated but the
status of the OUT output value (of the downstream Analog Input
function block) changes to BAD.
BLOCK_ERR read only Displays the active block error.
Note!
This parameter is available in all Transducer Blocks.
However, the block errors (apart from OUT OF SERVICE) are
only displayed via the BLOCK_ERR parameter of the Transducer
Block TRANSDUCER_DIAG (diagnosis, base index 1600).
Display:
OUT OF SERVICE
The block is in the Out of Service operating mode.
SIMULATION ACTIVE
Simulation is active via the Simulation - Measurand parameter
(see Page 128) in the Transducer Block TRANSDUCER_CH1 (flow
channel 1, base index 1200) or TRANSDUCER_CH2 (flow channel
2, base index 1300).
DEVICE NEEDS MAINTENANCE NOW
The device needs to be checked since an active device error is
pending. The cause of the error can be viewed in detail via the
"Diagnosis - Actual System Condition" parameter in the
Transducer Block TRANSDUCER_DIAG (diagnosis, base index
1600), (see Page 156).
UPDATE_
EVT
AUTO - OOS Displays whether static block data have been modified, including
date and time.
FOUNDATION Fieldbus parameters (Transducer Blocks, transmission blocks)
Parameter Write access
with operating
mode
(MODE_BLK)
Description

Table of Contents

Other manuals for Endress+Hauser Proline Prosonic Flow 93

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Endress+Hauser Proline Prosonic Flow 93 and is the answer not in the manual?

Endress+Hauser Proline Prosonic Flow 93 Specifications

General IconGeneral
BrandEndress+Hauser
ModelProline Prosonic Flow 93
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals