Diagnosis and troubleshooting Proline Prosonic Flow W 400 HART
140 Endress+Hauser
Diagnostic
number
Short text Remedy instructions Status
signal
[from the
factory]
Diagnostic
behavior
[from the
factory]
384 Transmitter circuit 1. Restart device
2. Check if failure recurs
3. Replace sensor electronic module
(ISEM)
F Alarm
385 Amplifier circuit 1. Restart device
2. Check if failure recurs
3. Replace sensor electronic module
(ISEM)
F Alarm
386 Time of flight 1. Restart device
2. Check if failure recurs
3. Replace sensor electronic module
(ISEM)
F Alarm
387 HistoROM data faulty Contact service organization F Alarm
Diagnostic of configuration
410 Data transfer failed 1. Retry data transfer
2. Check connection
F Alarm
412 Processing download Download active, please wait C Warning
431 Trim 1 required Carry out trim M Warning
437 Configuration
incompatible
1. Update firmware
2. Execute factory reset
F Alarm
438 Dataset different 1. Check dataset file
2. Check device parameterization
3. Download new device
parameterization
M Warning
441 Current output 1
saturated
1. Check current output settings
2. Check process
S Warning
1)
442 Frequency output 1 to n
saturated
1. Check frequency output settings
2. Check process
S Warning
1)
443 Pulse output 1 to n
saturated
1. Check pulse output settings
2. Check process
S Warning
1)
453 Flow override active Deactivate flow override C Warning
484 Failure mode simulation
active
Deactivate simulation C Alarm
485 Process variable
simulation active
Deactivate simulation C Warning
491 Current output 1
simulation active
Deactivate simulation C Warning
492 Frequency output 1 to n
simulation active
Deactivate simulation frequency
output
C Warning
493 Pulse output simulation
active
Deactivate simulation pulse output C Warning
494 Switch output 1 to n
simulation active
Deactivate simulation switch output C Warning
495 Diagnostic event
simulation active
Deactivate simulation C Warning
496 Status input 1
simulation active
Deactivate status input simulation C Warning
537 Configuration 1. Check IP addresses in network
2. Change IP address
F Warning