Proline Prosonic Flow W 400 HART Commissioning
Endress+Hauser 99
Assign flow direction check
→  100
Assign status
→  100
Switch-on value
→  100
Switch-off value
→  100
Switch-on delay
→  100
Switch-off delay
→  100
Failure mode
→  100
Invert output signal
→  100
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
Operating mode Define the output as a pulse,
frequency or switch output.
Pulse
*
Frequency
*
Switch
*
Switch output function The Switch option is selected
in the Operating mode
parameter.
Select function for switch
output.
Off
On
Diagnostic
behavior
Limit
Flow direction
check
Status
Assign diagnostic behavior In the Operating mode
parameter, the Switch
option is selected.
In the Switch output
function parameter, the
Diagnostic behavior option
is selected.
The output is switched on
(closed, conductive), if there is
a pending diagnostic event of
the assigned behavioral
category.
Alarm
Alarm or warning
Warning
Assign limit The Switch option is
selected in Operating mode
parameter.
The Limit option is selected
in Switch output function
parameter.
Select the variable to monitor
in case the specified limit value
is exceeded. If a limit value is
exceeded, the output is
switched on (conductive).
Off
Volume flow
Mass flow
Flow velocity
Sound velocity
Temperature
Density
Electronics
temperature
Signal strength
*
Signal to noise
ratio
*
Acceptance rate
*
Turbulence
*
Totalizer 1
Totalizer 2
Totalizer 3