Proline Prosonic Flow W 400 HART Electrical connection
Endress+Hauser 47
Signal transmission current output 0 to 20 mA/4 to 20 mA HART and additional outputs
and inputs
Order code for
"Output" and
"Input"
Terminal numbers
Output 1 Output 2 Output 3 Input
26 (+) 27 (-) 24 (+) 25 (-) 22 (+) 23 (-) 20 (+) 21 (-)
Option H Current output
4 to 20 mA HART
(active)
0 to 20 mA
(active)
Pulse/frequency
output
(passive)
Switch output
(passive)
-
Option I Current output
4 to 20 mA HART
(active)
0 to 20 mA
(active)
Pulse/frequency/
switch output
(passive)
Pulse/frequency/
switch output
(passive)
Status input
7.2.4 Preparing the measuring device
Carry out the steps in the following order:
1. Mount the sensor and transmitter.
2. Sensor connection housing: Connect sensor cable.
3. Transmitter: Connect sensor cable.
4. Transmitter: Connect cable for supply voltage.
NOTICE
Insufficient sealing of the housing!
Operational reliability of the measuring device could be compromised.
Use suitable cable glands corresponding to the degree of protection.
1. Remove dummy plug if present.
2. If the measuring device is supplied without cable glands:
Provide suitable cable gland for corresponding connecting cable.
3. If the measuring device is supplied with cable glands:
Observe requirements for connecting cables →  45.
7.3 Connecting the measuring device
L
WARNING
Risk of electric shock! Components carry dangerous voltages!
Have electrical connection work carried out by correspondingly trained specialists only.
Observe applicable federal/national installation codes and regulations.
Comply with local workplace safety regulations.
Observe grounding concept of the plant.
Never mount or wire the measuring device while it is connected to the supply voltage.
Before the supply voltage is applied, connect the protective ground to the measuring
device.
7.3.1 Connecting the sensor with transmitter
L
WARNING
Risk of damaging electronic components!
Connect the sensor and transmitter to the same potential equalization.
Only connect the sensor to a transmitter with the same serial number.