Proline Prosonic Flow W 400 HART Electrical connection
Endress+Hauser 47
Signal transmission current output 0 to 20 mA/4 to 20 mA HART and additional outputs
and inputs
Order code for
"Output" and
"Input"
Terminal numbers
Output 1 Output 2 Output 3 Input
26 (+) 27 (-) 24 (+) 25 (-) 22 (+) 23 (-) 20 (+) 21 (-)
Option H Current output
• 4 to 20 mA HART
(active)
• 0 to 20 mA
(active)
Pulse/frequency
output
(passive)
Switch output
(passive)
-
Option I Current output
• 4 to 20 mA HART
(active)
• 0 to 20 mA
(active)
Pulse/frequency/
switch output
(passive)
Pulse/frequency/
switch output
(passive)
Status input
7.2.4 Preparing the measuring device
Carry out the steps in the following order:
1. Mount the sensor and transmitter.
2. Sensor connection housing: Connect sensor cable.
3. Transmitter: Connect sensor cable.
4. Transmitter: Connect cable for supply voltage.
NOTICE
Insufficient sealing of the housing!
Operational reliability of the measuring device could be compromised.
‣
Use suitable cable glands corresponding to the degree of protection.
1. Remove dummy plug if present.
2. If the measuring device is supplied without cable glands:
Provide suitable cable gland for corresponding connecting cable.
3. If the measuring device is supplied with cable glands:
Observe requirements for connecting cables → 45.
7.3 Connecting the measuring device
L
WARNING
Risk of electric shock! Components carry dangerous voltages!
‣
Have electrical connection work carried out by correspondingly trained specialists only.
‣
Observe applicable federal/national installation codes and regulations.
‣
Comply with local workplace safety regulations.
‣
Observe grounding concept of the plant.
‣
Never mount or wire the measuring device while it is connected to the supply voltage.
‣
Before the supply voltage is applied, connect the protective ground to the measuring
device.
7.3.1 Connecting the sensor with transmitter
L
WARNING
Risk of damaging electronic components!
‣
Connect the sensor and transmitter to the same potential equalization.
‣
Only connect the sensor to a transmitter with the same serial number.