Parameter overview with brief description
Parameter Prerequisite Description User interface
Output current – Displays the current value currently
calculated for the current output.
3.59 to 22.5 mA
Measured current – Displays the current value currently
measured for the current output.
0 to 30 mA
Pulse output 1 to n The Pulse option is selected in the
Operating mode parameter parameter.
Displays the pulse frequency currently
output.
Positive floating-point
number
Output frequency 1 to n In the Operating mode parameter, the
Frequency option is selected.
Displays the value currently measured
for the frequency output.
0.0 to 12 500.0 Hz
Switch state 1 to n In the Operating mode parameter, the
Switch option is selected.
Displays the current switch output
status.
• Open
• Closed
11.4.5 "Totalizer" submenu
The Totalizer submenu contains all the parameters needed to display the current
measured values for every totalizer.
Navigation
"Diagnostics" menu → Measured values → Totalizer
‣
Totalizer
Totalizer 1 to n value
→ 123
Totalizer 1 to n overflow
→ 123
Parameter overview with brief description
Parameter Prerequisite Description User interface
Totalizer 1 to n value One of the following options is selected
in the Assign process variable
parameter (→ 106) of the Totalizer
1 to n submenu:
• Volume flow
• Mass flow
Displays the current totalizer counter
value.
Signed floating-point
number
Totalizer 1 to n overflow One of the following options is selected
in the Assign process variable
parameter (→ 106) of the Totalizer
1 to n submenu:
• Volume flow
• Mass flow
Displays the current totalizer overflow. Integer with sign
11.5 Adapting the measuring device to the process
conditions
The following are available for this purpose:
• Basic settings using theSetup menu (→ 83)
• Advanced settings using theAdvanced setup submenu (→ 104)