Electrical connection Proline Prosonic Flow W 400 HART
46 Endress+Hauser
Connecting cable between the transmitter and sensor
Sensor cable for sensor - transmitter
4
3
1
2
A0044949
Standard cable TPE: -40 to +80 °C (-40 to +176 °F)
TPE halogen-free: -40 to +80 °C (-40 to +176 °F)
PTFE: -40 to +130 °C (-40 to +266 °F)
Cable length (max.) 30 m (90 ft)
Cable lengths (available for
order)
5 m (15 ft), 10 m (30 ft), 15 m (45 ft), 30 m (90 ft)
Operating temperature Depends on the device version and how the cable is installed:
Standard version:
Cable - fixed installation
1)
: minimum –40 °C (–40 °F)
Cable - movable installation: minimum –25 °C (–13 °F)
1) Compare details under the row "Standard cable"
Cable diameter
Cable glands supplied:
For standard cable: M20 × 1.5 with cable  6 to 12 mm (0.24 to 0.47 in)
For reinforced cable: M20 × 1.5 with cable  9.5 to 16 mm (0.37 to 0.63 in)
(Plug-in) spring terminals for wire cross-sections 0.5 to 2.5 mm
2
(20 to 14 AWG)
7.2.3 Terminal assignment
Transmitter
The sensor can be ordered with terminals.
Connection methods available
Possible options for order code
"Electrical connection"
Outputs
Power
supply
Terminals Terminals Option A: coupling M20x1.5
Option B: thread M20x1.5
Option C: thread G ½"
Option D: thread NPT ½"
Supply voltage
Order code
"Power supply"
Terminal numbers terminal voltage Frequency range
Option L
(wide range power unit)
1 (L+/L), 2 (L-/N)
DC 24 V ±25%
AC 24 V ±25% 50/60 Hz, ±4 Hz
AC 100 to 240 V –15 to +10% 50/60 Hz, ±4 Hz