Commissioning Proline Prosonic Flow W 400 HART
90 Endress+Hauser
Parameter Prerequisite Description Selection / User
entry / User
interface
Factory setting
FlowDC inlet configuration The 1 measuring point - 2
signal paths option is selected
in Measuring point
configuration parameter.
Select FlowDC inlet
configuration.
• Off
• Single elbow
• Double elbow
• Double elbow 3D
• 45° bend
• 2 x 45° bend
• Concentric
diameter change
• Other
*
–
Intermediate pipe length The 1 measuring point - 2
signal paths option is selected
in Measuring point
configuration parameter.
Enter the length of the
intermediate pipe between the
two bends.
Positive floating-
point number
–
Inlet diameter • The 1 measuring point - 2
signal paths option is
selected in the Measuring
point configuration
parameter.
• The Concentric diameter
change option is selected in
the Inlet configuration
parameter.
Enter the outer diameter of the
pipe before the cross-section
change. For convenience, the
same measuring pipe wall
thickness as for the clamp-on
system is applied.
1 to 10 000 mm –
Transition length • In the Measuring point
configuration parameter,
the 1 measuring point - 2
signal paths option is
selected.
• In the Inlet configuration
parameter, the Concentric
diameter change option is
selected.
Enter length of the concentric
diameter change.
0 to 20 000 mm –
Inlet run The 1 measuring point - 2
signal paths option is selected
in Measuring point
configuration parameter.
Enter length of the available
straight inlet run.
0 to 300 000 mm –
Relative sensor position The 1 measuring point - 2
signal paths option is selected
in the Measuring point
configuration parameter and
the Off option is not selected
in FlowDC inlet configuration
parameter.
Shows the correct position for
the sensor.
• 90°
• 180°
–
Result sensor type / mounting type – Shows the selected sensor type
and (if applicable
automatically) selected
mounting type.
e.g. C-100-A option /
(2) V-mounting
option
–
Result sensor distance / measuring
aid
– Shows the calculated sensor
distance and vernier or wire
length (if applicable) required
for installation.
e.g. 201.3 mm / B 21 –
* Visibility depends on order options or device settings
10.4.4 Checking the installation status
The status of individual parameters can be checked in the Installation status submenu.