Commissioning Proline Prosonic Flow W 400 HART
96 Endress+Hauser
Configuring the pulse output
Navigation
"Setup" menu → Pulse/frequency/switch output 1 to n
Pulse/frequency/switch output
1 to n
Operating mode
→  96
Assign pulse output
→  96
Value per pulse
→  96
Pulse width
→  96
Failure mode
→  96
Invert output signal
→  96
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
Operating mode Define the output as a pulse,
frequency or switch output.
Pulse
*
Frequency
*
Switch
*
Assign pulse output The Pulse option is selected in
Operating mode parameter.
Select process variable for
pulse output.
Off
Volume flow
Mass flow
Pulse scaling The Pulse option is selected in
the Operating mode
parameter (→  96) and a
process variable is selected in
the Assign pulse output
parameter (→  96).
Enter quantity for measured
value at which a pulse is
output.
Positive floating
point number
Depends on country
and nominal
diameter
Pulse width The Pulse option is selected in
the Operating mode
parameter (→  96) and a
process variable is selected in
the Assign pulse output
parameter (→  96).
Define time width of the
output pulse.
0.05 to 2 000 ms
Failure mode The Pulse option is selected in
the Operating mode
parameter (→  96) and a
process variable is selected in
the Assign pulse output
parameter (→  96).
Select output behavior in the
event of a device alarm.
Actual value
No pulses
Invert output signal Invert the output signal. No
Yes
* Visibility depends on order options or device settings