Proline Prosonic Flow W 400 HART System integration
Endress+Hauser 81
9.3 Other settings
Burst mode functionality in accordance with HART 7 Specification:
Navigation
"Expert" menu → Communication → HART output → Burst configuration → Burst
configuration 1 to n
‣
Burst configuration 1 to n
Burst mode 1 to n
→ 81
Burst command 1 to n
→ 81
Burst variable 0
→ 82
Burst variable 1
→ 82
Burst variable 2
→ 82
Burst variable 3
→ 82
Burst variable 4
→ 82
Burst variable 5
→ 82
Burst variable 6
→ 82
Burst variable 7
→ 82
Burst trigger mode
→ 82
Burst trigger level
→ 82
Min. update period
→ 82
Max. update period
→ 82
Parameter overview with brief description
Parameter Description Selection / User entry
Burst mode 1 to n Activate the HART burst mode for burst message X. • Off
• On
Burst command 1 to n Select the HART command that is sent to the HART master. • Command 1
• Command 2
• Command 3
• Command 9
• Command 33
• Command 48