System integration Proline Prosonic Flow W 400 HART
80 Endress+Hauser
Dynamic variables Measured variables
(HART device variables)
Primary dynamic variable (PV) Volume flow
Secondary dynamic variable (SV) Totalizer 1
Tertiary dynamic variable (TV) Totalizer 2
Quaternary dynamic variable (QV) Totalizer 3
The assignment of the measured variables to the dynamic variables can be modified and
assigned as desired via local operation and the operating tool using the following
parameters:
Expert → Communication → HART output → Output → Assign PV
Expert → Communication → HART output → Output → Assign SV
Expert → Communication → HART output → Output → Assign TV
Expert → Communication → HART output → Output → Assign QV
The following measured variables can be assigned to the dynamic variables:
Measured variables for PV (primary dynamic variable)
Measured variables which are generally available:
Volume flow
Mass flow
Flow velocity
Sound velocity
Electronics temperature
Additional measured variables with the Heartbeat Verification + Monitoring application
package:
Signal strength
Signal to noise ratio
Acceptance rate
Turbulence
Measured variables for SV, TV, QV (secondary, tertiary and quaternary dynamic
variable)
Measured variables which are always available:
Volume flow
Mass flow
Flow velocity
Sound velocity
Electronics temperature
Totalizer 1
Totalizer 2
Totalizer 3
HART input
Current input 1
6)
Current input 2
6)
Current input 3
6)
Additional measured variables with the Heartbeat Verification + Monitoring application
package:
Signal strength
Signal to noise ratio
Acceptance rate
Turbulence
6) Visible depending on the order options or device settings