Proline Prosonic Flow W 400 HART Mounting procedure
Endress+Hauser 43
6.2.5 Turning the display module
The display module can be turned to optimize display readability and operability.
TX 20
4 x
1.
2.
PUSH TO
REMOVE
PUSH TO
REMOVE
3.
4.
A0046804
1. Loosen the fixing screws of the housing cover.
2. Open the housing cover.
3. Unlock the display module.
4. Pull out the display module and turn it to the desired position in increments of 90°.
Mounting the transmitter housing
L
WARNING
Excessive tightening torque applied to the fixing screws!
Damage to the transmitter.
Tighten the fixing screws with the specified torques.
1. Insert the display module and lock it when doing so.
2. Close the housing cover.
3. Tighten the fixing screws of the housing cover: tightening torque for aluminum
housing 2.5 Nm (1.8 lbf ft) – plastic housing 1 Nm (0.7 lbf ft).
6.3 Post-mounting check
Is the measuring device undamaged (visual inspection)?
Does the measuring device correspond to the measuring point specifications?
For example:
Process temperature →  163
Inlet run conditions
Ambient temperature
Measuring range
Has the correct orientation for the sensor been selected →  20?
According to sensor type
According to medium temperature
According to medium properties (outgassing, with entrained solids)
Are the sensors correctly connected to the transmitter (upstream/downstream) ?
Are the sensors correctly mounted (distance, 1 traverse, 2 traverses) →  24?
Is the tag name and labeling correct (visual inspection)?
Is the device sufficiently protected from precipitation and direct sunlight?