Commissioning Proline Prosonic Flow W 400 HART
92 Endress+Hauser
10.4.5 Configuring the status input
The Status input submenu guides the user systematically through all the parameters that
have to be set for configuring the status input.
The submenu only appears if the device was ordered with a status input .
Navigation
"Setup" menu → Status input
Structure of the submenu
‣
Status input
Assign status input
→ 92
Active level
→ 92
Response time status input
→ 92
Parameter overview with brief description
Parameter Description Selection / User entry
Assign status input Select function for the status input. • Off
• Reset totalizer 1
• Reset totalizer 2
• Reset totalizer 3
• Reset all totalizers
• Flow override
Active level Define input signal level at which the assigned function is
triggered.
• High
• Low
Response time status input Define the minimum amount of time the input signal level must
be present before the selected function is triggered.
5 to 200 ms