Commissioning Proline Prosonic Flow W 400 HART
94 Endress+Hauser
Parameter Prerequisite Description Selection / User
entry
Factory setting
Lower range value output In Current span parameter
(→  93), one of the
following options is selected:
4...20 mA NE (3.8...20.5
mA)
4...20 mA US (3.9...20.8
mA)
4...20 mA (4...20.5 mA)
0...20 mA (0...20.5 mA)
Enter lower range value for the
measured value range.
Signed floating-point
number
Depends on country:
m³/h
ft³/h
Upper range value output In Current span parameter
(→  93), one of the
following options is selected:
4...20 mA NE (3.8...20.5
mA)
4...20 mA US (3.9...20.8
mA)
4...20 mA (4...20.5 mA)
0...20 mA (0...20.5 mA)
Enter upper range value for
the measured value range.
Signed floating-point
number
Depends on country
and nominal
diameter
Fixed current The Fixed current option is
selected in the Current span
parameter (→  93).
Defines the fixed output
current.
0 to 22.5 mA 22.5 mA
Damping current output A process variable is selected
in the Assign current output
parameter (→  93) and one
of the following options is
selected in the Current span
parameter (→  93):
4...20 mA NE (3.8...20.5
mA)
4...20 mA US (3.9...20.8
mA)
4...20 mA (4...20.5 mA)
0...20 mA (0...20.5 mA)
Enter time constant for output
damping (PT1 element).
Damping reduces the effect of
fluctuations in the measured
value on the output signal.
0.0 to 999.9 s
Failure behavior current output A process variable is selected
in the Assign current output
parameter (→  93) and one
of the following options is
selected in the Current span
parameter (→  93):
4...20 mA NE (3.8...20.5
mA)
4...20 mA US (3.9...20.8
mA)
4...20 mA (4...20.5 mA)
0...20 mA (0...20.5 mA)
Select output behavior in the
event of a device alarm.
Min.
Max.
Last valid value
Actual value
Fixed value
Failure current The Defined value option is
selected in the Failure mode
parameter.
Enter current output value in
alarm condition.
0 to 22.5 mA
* Visibility depends on order options or device settings
10.4.7 Configuring the pulse/frequency/switch output
The Pulse/frequency/switch output wizard guides you systematically through all the
parameters that can be set for configuring the selected output type.
Navigation
"Setup" menu → Pulse/frequency/switch output
Pulse/frequency/switch output