Proline Prosonic Flow W 400 HART Commissioning
Endress+Hauser 93
10.4.6 Configuring the current output
The Current output wizard guides you systematically through all the parameters that have
to be set for configuring the current output.
Navigation
"Setup" menu → Current output 1
Current output 1
Process variable current output
(0359–1)
→  93
Current range output (0353–1)
→  93
Lower range value output (0367–1)
→  94
Upper range value output (0372–1)
→  94
Fixed current (0365–1)
→  94
Damping current output (0363–1)
→  94
Failure behavior current output
(0364–1)
→  94
Failure current (0352–1)
→  94
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
Process variable current output Select the process variable for
the current output.
Off
*
Volume flow
Mass flow
Flow velocity
Sound velocity
Temperature
Density
Signal strength
*
Signal to noise
ratio
*
Acceptance rate
*
Turbulence
*
Electronics
temperature
Current range output Select current range for
process value output and
upper/lower level for alarm
signal.
4...20 mA NE
(3.8...20.5 mA)
4...20 mA US
(3.9...20.8 mA)
4...20 mA (4...20.5
mA)
0...20 mA (0...20.5
mA)
Fixed value
Depends on country:
4...20 mA NE
(3.8...20.5 mA)
4...20 mA US
(3.9...20.8 mA)