Proline Prosonic Flow W 400 HART Commissioning
Endress+Hauser 89
Parameter Prerequisite Description Selection / User
entry / User
interface
Factory setting
Pipe circumference The Pipe circumference
option is selected in the Pipe
dimensions parameter.
Define the pipe circumference. 30 to 62 800 mm –
Pipe outer diameter The Diameter option is
selected in Pipe dimensions
parameter.
Define the outer diameter of
the pipe.
0 to 20 000 mm –
Pipe wall thickness – Enter the pipe wall thickness. Positive floating
point number
3 mm
Liner material – Select liner material. • None
• Cement
• Rubber
• Epoxy resin
• Unknown liner
material
–
Liner sound velocity The Unknown liner material
option is selected in the Liner
material parameter.
Define the sound velocity of
liner material.
800.0 to 3 800.0 m/s –
Liner thickness One of the following options is
selected in the Liner material
parameter:
• Cement
• Rubber
• Epoxy resin
• Unknown liner material
Define the thickness of liner. 0 to 100 mm –
Sensor type – Select sensor type. • C-030-A
• C-050-A
• C-100-A
• C-100-B
• C-100-C
• C-200-A
• C-200-B
• C-200-C
• C-500-A
As per order
Sensor coupling The following option is
selected in Sensor type
parameter:
• C-030-A
• C-050-A
• C-100-A
• C-100-B
• C-100-C
• C-200-A
• C-200-B
• C-200-C
• C-500-A
Select coupling medium. • Coupling pad
• Coupling paste
–
Mounting type – Select the number of traverses
(number of times the signal
passes through the medium).
• (1) direct option: Sensor
arrangement with 1 traverse
• (2) V-mounting option:
Sensor arrangement with 2
traverses
• (3) Z-Mounting option:
Sensor arrangement with 3
traverses
• (4) W-mounting option:
Sensor arrangement with 4
traverses
• 1 traverse
• 2 traverses
• 3 traverses
• 4 traverses
• Automatic
Automatic
Cable length – Enter length of sensor cables. 0 to 200 000 mm As per order